Abstract
Edge data centres and small server rooms are widely embedded in non-domestic buildings, yet their cooling systems remain energy intensive and under-optimised. This study reports the operational evidence of dew-point cooling (DPC) in a live edge data centre in Hull, the UK. The units feature a heat and mass exchanger, high-performance wetting medium, and intermittent water supply. Results from representative operating periods showed that the DPC system delivered stable cooling with low electrical input, achieving a Coefficient of Performance (COP) of up to 40. The monitored hourly profiles also showed important maintenance periods, with a legionella monitoring scheme as a routine risk management. These findings provide evidence to demonstrate that the DPC system is an efficient and practical cooling solution for small edge data centres and support its wider application in similar built environments.
| Original language | English |
|---|---|
| Number of pages | 4 |
| Journal | Energy Proceedings |
| Volume | 67 |
| DOIs | |
| Publication status | Published - 2026 |
| Event | 17th International Conference on Applied Energy, ICAE 2025 - Bangkok, Thailand Duration: 8 Dec 2025 → 12 Dec 2025 |
Keywords
- Dew point evaporative cooling
- Edge data centre
- Energy Efficiency
- Field performance